Kitchen electrical requirements
The kitchen concentrates the heaviest plug-in loads in a house — toaster, kettle, microwave, coffee maker — plus fixed appliances whose supply must be checked separately. It is also where the NEC is the most specific, which makes it the room to plan first.
Separate countertop supply, lighting and appliances.
Follow a kitchen example from the layout to circuit groups.
Review islands and cabinet details separately.
Two small-appliance circuits, minimum
At least two 20 A small-appliance branch circuits serve all the receptacles of the kitchen, pantry, breakfast room and dining room, including the countertop ones (210.11(C)(1) and 210.52(B)). The countertop must be served by at least two of them, so two high-wattage appliances can run side by side.
These circuits carry no lighting and no other outlets. The usual exceptions are a refrigerator on its own 15 A or larger circuit, a clock receptacle and the igniter of a gas range.
The numbered receptacles illustrate two SA groups. Locations and counts are schematic: wall-counter spacing, island provisions and appliance circuits need their own review.
Open full-size diagram ↗Countertop receptacles
Each wall countertop or work-surface space 12 in or wider needs a receptacle, with no point along the wall line more than 24 in from one (210.52(C)). Islands and peninsulas have their own rules, which changed in 2023. These are spacing rules: draw them carefully on a dimensioned plan, since Planelico does not measure distances on a PDF.
GFCI and AFCI in the kitchen
Since 2023, all kitchen receptacles need GFCI protection, not only those serving the countertop. Kitchen 120 V, 10 A, 15 A and 20 A branch circuits also need AFCI protection, so a dual function breaker is the simplest way to protect each small-appliance circuit. The dishwasher needs GFCI wherever it is, and the range needs it too in the 2023 edition.
Dedicated appliance circuits
Typical kitchen circuits, to be confirmed against each appliance’s nameplate and installation instructions:
- Range or cooktop: 240 V, 40 or 50 A (40 A minimum for a range of 8.75 kW or more).
- Wall oven: 240 V, often 30 A.
- Dishwasher: 120 V, 15 or 20 A, often with the disposal on its own circuit.
- Over-the-range microwave: 120 V, 20 A dedicated is common practice.
- Refrigerator: 120 V, 15 or 20 A individual circuit is allowed and common.
Lighting
A kitchen needs a wall-switch-controlled lighting outlet; unlike a bedroom, a switched receptacle does not count. Because small-appliance circuits cannot carry lighting, kitchen lighting goes on a separate lighting or general-purpose circuit.
Planning the kitchen in Planelico
Mark the kitchen, dining room and pantry with their room types. Planelico puts all their receptacles on at least two 20 A small-appliance circuits, keeps lighting off them, gives each fixed appliance its own circuit in AWG, and protects every kitchen breaker with GFCI or dual function as required. If you merge the small-appliance circuits into one, the validation blocks it.
Plan the island separately from the wall countertops
The 2023 NEC treats islands and peninsulas differently from wall countertops. Under 210.52(C)(2), a receptacle serving an island or peninsula is optional, but provisions for a future receptacle are needed when none is installed. Confirm the permitted arrangement and any local amendments with the AHJ.
Keep an island note on the plan even when no receptacle is proposed. A countertop appliance needs a usable supply location, and the outlet arrangement must be coordinated with the cabinet and countertop design. Planelico does not automatically check countertop geometry or decide how the future provision is constructed.
Example: two countertop circuits and a separate appliance list
For a kitchen with a breakfast area, show which general receptacles belong to the small-appliance circuits and keep their lighting separate. Label the proposed groups clearly, for example “Kitchen SA 1” and “Kitchen / breakfast SA 2,” then review how countertop appliances are likely to be used together.
List the refrigerator, dishwasher, disposal, microwave, range and any wall oven independently. Two required small-appliance circuits are a minimum category of supply; they do not settle the needs of every appliance. Individual circuits can be required by the load or manufacturer, or selected as a design choice.
Follow a device from its room to its proposed supply. GEN is general-purpose, SA is small-appliance, and DF combines AFCI and GFCI. This is a relationship diagram, not installation wiring.
Open full-size diagram ↗| Item | Illustrative assignment | Decision still needed |
|---|---|---|
| Wall countertop receptacles | SA 1 and SA 2; 20 A each | Spacing on the dimensioned design |
| Dining-area general receptacles | Eligible SA group | Review grouping and anticipated loads |
| Ceiling / under-cabinet lights | Separate from SA circuits | Switching, fixture ratings and actual circuit |
| Dishwasher / disposal | Review individual appliance circuits | Instructions, load and permitted sharing |
| Range / wall oven | Appliance circuit sized separately | Actual voltage, nameplate and installation instructions |
| Island / peninsula | Separate layout note | Receptacle arrangement or required future provision |
Coordinate outlets with cabinets before rough-in
Check the appliance schedule against the latest cabinet elevations. A receptacle that looks clear on a floor plan can end up behind a drawer, inside an inaccessible appliance opening or in conflict with the backsplash. Record intended mounting locations and any installation instructions that affect access.
Leave a revision note when a homeowner changes from a gas range to electric cooking or adds a second oven. Update the equipment list, circuit proposal and service load calculation together; changing the symbol on the floor plan is only the first step.
- Mark wall countertop segments, sink and cooking locations on a dimensioned drawing.
- Show the island or peninsula arrangement and any future outlet provision.
- Keep small-appliance circuit assignments distinct from lighting.
- Confirm the selected appliances before final breaker and cable selection.
Worked example: a wall counter, breakfast area and island
Use the illustrated L-shaped kitchen as a grouping exercise. Numbered receptacles represent possible SA 1 and SA 2 assignments. Place the real sink, range and wall-counter segments on the dimensioned drawing, then perform the spacing review separately. The handful of illustrated devices is not a sufficient outlet count for an actual kitchen.
Add the breakfast-area receptacles to the planning list and review their eligible SA supply. Keep ceiling and under-cabinet lighting outside those small-appliance circuits. List each fixed appliance separately, with its model, voltage and installation instructions. An individual circuit proposed by the generator should be checked against that equipment rather than treated as a universal kitchen rule.
For the island, state whether a receptacle is proposed and how the adopted 2023 future-provision requirement is addressed when none is installed. Coordinate the arrangement with the cabinet maker and electrician. A generic island symbol does not specify a listed countertop assembly or an accessible installation location.
Change example: replace a gas range with electric cooking
Changing the cooking appliance affects more than the label on the plan. Record the selected electric appliance and check whether it is a freestanding range, separate cooktop or wall oven. Its nameplate and installation instructions determine the branch-circuit review; do not reuse a rating from an unrelated sample kitchen.
Ask the electrician to review the route, existing panel suitability, required protection and service load. Update the appliance list, schedule and estimate together. If the model is still undecided, make that an explicit pricing assumption or open item so that the quote does not silently include an installation for the wrong equipment.
Quick method with Planelico
- 1
Qualify kitchen, dining and pantry
Their receptacles feed the small-appliance circuits.
- 2
Place countertop receptacles
Follow the 24 in / 12 in rules on your dimensioned plan.
- 3
Add the appliances
Range, dishwasher, microwave, refrigerator, disposal.
- 4
Generate and review
Two SA circuits, dedicated circuits and DF breakers.