Protection · 9 min

GFCI and AFCI requirements by room

GFCI and AFCI protect against two different hazards. A GFCI trips on current leaking to ground — the shock risk near water. An AFCI trips on the signature of an arcing fault — the fire risk in damaged cords and wiring. The NEC decides where each one is required, and the list grows with almost every edition.

Updated: November 2026
01

Compare bedroom, bathroom, kitchen and laundry examples.

02

Distinguish AFCI, GFCI and dual function devices.

03

Review the complete circuit, not only its label.

Where GFCI is required (210.8)

In dwellings, 210.8(A) requires GFCI protection for 125 V through 250 V receptacles supplied by single-phase circuits of 150 V or less to ground, in these locations:

  • Bathrooms.
  • Garages and accessory buildings with a floor at or below grade.
  • Outdoors.
  • Crawl spaces at or below grade, and basements.
  • Kitchens — all receptacles, not only countertop ones, since 2023.
  • Within 6 ft of a sink, bathtub or shower.
  • Laundry areas, boathouses and indoor damp or wet locations.
Bedroom, bathroom, kitchen and laundry examples comparing AFCI, GFCI and dual function protection

Typical NEC 2023 examples for the circuits described. Review every location and appliance supplied, the adopted code and any amendments; these four examples are not an exhaustive protection chart.

Open full-size diagram ↗

All outdoor outlets, HVAC included (210.8(F))

Beyond receptacles, 210.8(F) requires GFCI protection for every outdoor outlet of a dwelling supplied at 150 V or less to ground and 50 A or less — including garages at or below grade, accessory buildings and boathouses, and hard-wired equipment. Lighting outlets are generally exempt under 210.8(F), except crawl-space lighting covered by 210.8(C).

The published exception for listed HVAC equipment carried a September 1, 2026 expiration date. Its extension has been the subject of NFPA interim-amendment proceedings. Before specifying protection for an outdoor heat pump or air conditioner, verify the current NFPA text, issued amendments and local adoption with the AHJ; this guide does not establish the applicable exception status.

Appliances that need GFCI wherever they are (210.8(D))

Some appliances require GFCI protection regardless of the room, whether they are cord-and-plug connected or hard-wired: dishwashers, and in the 2023 edition electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, microwave ovens and sump pumps, rated 150 V or less to ground and 60 A or less. In practice, this means two-pole GFCI breakers for the range and dryer circuits.

Older editions had a shorter list: check the edition your jurisdiction enforces.

Where AFCI is required (210.12)

All 120 V, single-phase, 10 A, 15 A and 20 A branch circuits supplying outlets or devices in these areas need AFCI protection: kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas and similar rooms.

Bathrooms, garages and outdoors are not on the AFCI list. When a circuit in those areas is modified, replaced or extended in an AFCI area, the alteration provisions of 210.12(E) must be reviewed, including their exceptions.

When both apply: dual function breakers

Kitchens and laundry areas need both. A dual function (DF) breaker provides GFCI and AFCI protection in one device and is the simplest way to cover a kitchen small-appliance circuit or a laundry circuit. A dishwasher circuit in the kitchen is the same case: GFCI because of the appliance, AFCI because of the room.

Breaker or receptacle?

GFCI protection can come from a GFCI receptacle protecting the downstream outlets, or from a GFCI breaker protecting the whole circuit. AFCI is most often provided by the breaker; the NEC also allows outlet branch-circuit AFCIs under specific conditions.

Planelico places the protection at the breaker, which keeps the panel directory readable and works for every outlet type. Your electrician may choose receptacles instead where it is cheaper.

How Planelico assigns protection

Each circuit’s protection is derived from the room types it serves and the appliances on it: GFCI, AFCI, dual function or standard. A lighting-only circuit does not get GFCI from its room, since 210.8(A) covers receptacles; a hard-wired appliance such as a water heater does not get room-based GFCI either. The rules based on distance to a sink or tub cannot be measured on a PDF and are left to the installer.

Load center and sample circuit schedule showing descriptions, amperage and protection

An illustrative directory excerpt, not the complete panel for the house. Match final descriptions and breaker positions to the installed equipment; the EV row does not specify every protection detail.

Open full-size diagram ↗

Three examples of protection decisions

A bedroom circuit supplying general receptacles and lighting normally needs AFCI protection under the dwelling rules. A bathroom receptacle circuit needs GFCI protection; the bathroom location alone does not create the living-area AFCI requirement. In a kitchen or laundry area, the relevant 120 V circuits can need both protections.

Check everything supplied by a circuit, not just its name. A circuit labeled “hallway” may also supply a receptacle elsewhere. Mixed locations and particular appliances can add protection requirements, so the room labels and device assignments must describe the real installation.

NEC 2023 protection examples — not an exhaustive installation checklist
Circuit exampleProtection to reviewReason
Bedroom, 120 V / 20 AAFCILiving-area circuit under 210.12
Bathroom receptaclesGFCIBathroom location under 210.8
Kitchen SA, 120 V / 20 AGFCI + AFCI; DF is one approachKitchen receptacles and dwelling AFCI provisions
Laundry, 120 V / 20 AGFCI + AFCI; DF is one approachLaundry location and dwelling AFCI provisions
Electric range, 240 VGFCI within 210.8(D) scopeDo not apply the 120 V AFCI rule to every 240 V appliance

Combination AFCI and dual function are different labels

A combination-type AFCI detects the arc-fault conditions covered by its listing. The word “combination” does not mean it also provides GFCI protection. A dual function device combines AFCI and GFCI functions. Read the manufacturer’s markings rather than relying on a product name that sounds similar.

Planelico uses DF for dual function in the proposed panel schedule. That abbreviation explains the selected protection; it is not a manufacturer part number. The electrician still needs to choose a listed breaker suitable for the actual load center.

How to approach an existing circuit during a remodel

Record what is already installed before planning extensions: the panel model, breaker rating and protection, the devices supplied, and any existing GFCI receptacles. Replacing a receptacle, extending wiring and installing a new circuit can have different requirements under the adopted code.

Do not assume the age of the house exempts the proposed work, or that every untouched circuit must automatically be rebuilt. Ask the AHJ which provisions apply to the actual alteration. If a protective device trips, have the cause investigated rather than omitting the protection from the design.

Worked review: one kitchen circuit, two protective functions

Consider a 120 V, 20 A small-appliance circuit supplying eligible kitchen receptacles. Under the NEC 2023 provisions discussed here, review both ground-fault and arc-fault protection. In the Planelico schedule, a dual function breaker is the selected design approach. The label DF should therefore be read as two intended functions, not as a cable type or a breaker manufacturer.

Trace the served devices before choosing products. Confirm the kitchen location, any extension into eligible dining or pantry receptacles, and any equipment-specific requirements. Then have the electrician select compatible listed equipment and verify the permitted protection arrangement under the adopted code. The four-room illustration is a starting point for that review, not a complete purchasing list.

If the scope later adds a fixed appliance, review the appliance separately. A 240 V appliance does not automatically inherit the 120 V small-appliance circuit arrangement merely because it is in the kitchen. Its voltage, rating and the applicable GFCI provisions must be considered on their own.

Write protection notes that are useful to the installer

A useful note says which circuit and served area are involved, the intended protective function and the decision that remains open. For example: “Kitchen SA 1 — proposed DF protection; confirm breaker listing for existing load center.” This distinguishes the design intent from equipment selection.

Avoid notes such as “all outlets protected” when no one has traced the downstream devices or confirmed the installed arrangement. On an existing installation, have the electrician verify what a protective device actually supplies. The drawing should record the review result rather than convert an assumption into a compliance statement.

Quick method with Planelico

  1. 1

    Qualify the rooms

    Room types drive the protection of every circuit.

  2. 2

    Place appliances

    Dishwasher, range, dryer: they bring their own GFCI requirement.

  3. 3

    Generate the load center

    Each breaker shows GFCI, AFCI, DF or standard.

  4. 4

    Review the directory

    Check the protection column before ordering breakers.

Frequently asked questions

Do bedrooms need GFCI?
Not under 210.8(A), unless a receptacle is within 6 ft of a sink. Bedrooms need AFCI protection.
Does a refrigerator need GFCI?
In a kitchen, yes: since 2023 all kitchen receptacles need GFCI protection, including the one behind the refrigerator.
Is a dual function breaker required?
No device is mandated; protection is. A dual function breaker is simply the easiest way to provide both GFCI and AFCI on one circuit.
Do garage receptacles need AFCI?
Garages are not on the 210.12 list, so GFCI is required but AFCI is not.
Is a combination AFCI the same as a dual function breaker?
No. Combination-type AFCI describes arc-fault protection. Dual function combines AFCI and GFCI. Check the listed functions and panel compatibility of the selected product.
Does a room label settle protection for the whole circuit?
No. Review all locations and equipment supplied by the circuit. A device in another area or an appliance-specific rule can add a protection requirement.

Official sources

Related guides

Kitchen electrical requirementsNEC electrical plan for a houseGenerate a load center from your floor plan

Build your electrical plan online