EV charger circuit sizing for a Level 2 charger
A Level 2 charger is the biggest continuous load most houses will ever add. It runs for hours at full current, which is exactly why the NEC sizes its circuit with a margin — and why it deserves a place on the electrical plan before the garage wall is finished.
An individual 240 V circuit
Article 625 treats EV charging as a continuous load. The charger needs an individual branch circuit with no other outlets on it (625.40). Most home chargers run on 240 V, between the two legs of the split-phase service.
The 125 % rule
The overcurrent protection must be at least 125 % of the charger’s maximum current (625.41). Start from the power: a 7.4 kW charger draws about 31 A at 240 V; 125 % gives 38.5 A, so the next standard breaker is 40 A. A 48 A charger needs a 60 A breaker.
- 3.7 kW (about 16 A): 20 A breaker, 12 AWG copper.
- 7.4 kW (about 31 A): 40 A breaker, 8 AWG copper.
- 9.6 kW (40 A): 50 A breaker, 6 AWG copper.
- 11.5 kW (48 A): 60 A breaker, 4 AWG copper.
- 19.2 kW (80 A): 100 A breaker, 1 AWG copper — check that the service can carry it.
Plug-in or hardwired?
A plug-in charger on a NEMA 14-50 or 6-50 receptacle is convenient, but the receptacle needs GFCI protection (625.54), and a receptacle is not designed for hours of full load every night. A hardwired charger is often the better choice above 32 A.
In a garage or outdoors, 210.8(F) also asks for GFCI protection on hard-wired outlets up to 50 A. Some jurisdictions accept the charger’s built-in protection instead: ask your inspector.
Can the service handle it?
Adding 40 A of continuous load to a 100 A service with an electric range, dryer and water heater can exceed its capacity. An Article 220 load calculation answers the question; load management systems that throttle the charger when the house is busy are an alternative to a service upgrade.
Planning the charger in Planelico
Place the wallbox in the garage or outdoors and choose its power: 7.2, 9.6, 11.5 or 19.2 kW. Planelico creates the individual circuit, sizes the breaker at 125 % with the next standard rating, picks the wire size in AWG, and adds a point to check reminding the installer of the Article 625 requirements. Wire size must still be confirmed for the actual run length and voltage drop.
Quick method with Planelico
- 1
Place the charger
Next to the parking space, on the side of the car’s charging port.
- 2
Choose the power
3.7, 7.4 kW or more, depending on the car and the service.
- 3
Draw the route
From the load center to the charger.
- 4
Generate and export
Individual circuit at 125 %, ready for your electrician’s quote.
Frequently asked questions
Official sources
Build your electrical plan online
Import your PDF plan, drop the electrical symbols and export a clean document to share.